Violation Detail
Standard Cited: 19100303 B07 III General.
Inspection Nr: 1510073.015
Citation: 01008
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $2,926.00
Current Penalty: $1,463.00
Issuance Date: 05/20/2021
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 06/16/2021
Gravity: 5
Report ID: 0728500
Contest Date: 06/28/2021
Final Order: 11/29/2021
Related Event Code (REC): C
Emphasis:
Substance: 8870
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 11/29/2021 | $1,463.00 | 06/16/2021 | Serious | |
Penalty | C: Contested | 06/30/2021 | $2,926.00 | 06/16/2021 | Serious | |
Penalty | Z: Issued | 05/20/2021 | $2,926.00 | 06/16/2021 | Serious |
Text For Citation: 01 Item/Group: 008 Hazard:
29 CFR 1910.303(b)(7)(iii): Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces, may not be damaged or contaminated by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive residues. At the workplace located at 1020 West 29th Street, Kansas City, Missouri 64108, employees were exposed to possible shock, burns, fire or potential electrocution. The electrical box located behind the Bolton Tools TV 300 cut off machine was open and contaminated with foreign material. The foreign material was generated from the operation of the Bolton Tools TV 300 cut off machine.