Violation Detail
Standard Cited: 19100106 E06 II Flammable liquids.
This violation item has been deleted.
Inspection Nr: 1291102.015
Citation: 01008
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,174.00
Current Penalty: $0.00
Issuance Date: 07/24/2018
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 07/30/2018
Gravity: 5
Report ID: 0625400
Contest Date:
Final Order: 08/24/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/24/2018 | $0.00 | 07/30/2018 | Serious | |
Penalty | Z: Issued | 07/24/2018 | $5,174.00 | 07/30/2018 | Serious |
Text For Citation: 01 Item/Group: 008 Hazard:
29 CFR 1910.106(e)(6)(ii):Category 1 or 2 flammable liquids, or Category 3 flammable liquids with a flashpoint below 100 degree F (37.8 degree C), were dispensed into containers without the nozzle and containers being electrically interconnected: On or about January 31, 2018, near the paint storage area, employees were transferring flammable paint thinner into small metal containers to use at the paint hopper. The smaller metal cans and 55 gallon drum were not bonded, exposing employees to the hazards of fire.