Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1145409.015
Citation: 01008
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $8,017.00
Current Penalty: $5,785.00
Issuance Date: 11/04/2016
Nr Instances: 3
Nr Exposed: 4
Abatement Date:
Gravity: 5
Report ID: 0213400
Contest Date:
Final Order: 12/02/2016
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/02/2016 | $5,785.00 | Serious | ||
Penalty | Z: Issued | 11/04/2016 | $8,017.00 | Serious |
Text For Citation: 01 Item/Group: 008 Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: Santec Inc./Linden, NJ- Production Area/Section #2: An electrical relocatable power tap (RPT), also known as an extension block, power bar, plug board, and by many other variations, was not installed in accordance with manufacturer's listing. A relocatable power tap was used in an industrial setting and not as intended: a) Relocatable Power Tap (RPT) was used in section 2 (on the West wall, dividing section 1 from section 2) to power a 16 gauge extension cord which provided power to additional equipment. b) Two Relocatable Power Taps (RPT) used in section 2 (by employee desk area) were powered by extension cords and also provided power to additional equipment c) Relocatable Power Tap (RPT) in section 2 (East wall, by the mixer used for solids) was powered by extension cords Violation observed on or about May 5, 2016.