Violation Detail
Standard Cited: 19100272 J03 Grain handling facilities.
Inspection Nr: 1123539.015
Citation: 01008
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $7,000.00
Current Penalty: $6,506.00
Issuance Date: 07/22/2016
Nr Instances: 1
Nr Exposed: 30
Abatement Date:
Gravity:
Report ID: 0418200
Contest Date:
Final Order: 08/10/2016
Related Event Code (REC):
Emphasis:
Substance: E101
Substance: E200
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/10/2016 | $6,506.00 | Serious | ||
Penalty | Z: Issued | 07/22/2016 | $7,000.00 | Serious |
Text For Citation: 01 Item/Group: 008 Hazard:
29 CFR 1910.272(j)(3): Compressed air was used to blow dust from ledges, walls, and other areas in grain handling facilities when machinery presenting ignition sources was not shut down, and/or when all other known potential ignition sources in the area were removed or controlled: (a)Throughout the mill- On or about February 7, 2016, and times prior, employees were exposed to fire and explosion hazards from combustible dust in that the employer failed to ensure compressed air was not utilized for cleaning walls and floors while machinery such as Hammer mills, drag and screw conveyors, bucket elevators, pellet mills, electric motors, and motor terminal boxes were in operation, This presented potential ignition sources from overheated motors, drive belts, overheated bearings, and electrical sparks.