Violation Detail
Standard Cited: 19100305 B01 II Wiring methods, components, and equipment for general use.
Inspection Nr: 1598521.015
Citation: 01007D
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $4,144.00
Current Penalty: $0.00
Issuance Date: 11/08/2022
Nr Instances: 1
Nr Exposed: 5
Abatement Date:
Gravity: 5
Report ID: 0111700
Contest Date:
Final Order: 12/16/2022
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 12/16/2022 | $0.00 | Serious | ||
Penalty | Z: Issued | 11/08/2022 | $4,144.00 | Serious |
Text For Citation: 01 Item/Group: 007D Hazard:
29 CFR 1910.305(b)(1)(ii): Unused openings in boxes, cabinets, or fittings were not effectively closed: a. Site- Employees were not protected from electric shock and burns where knockouts in the panel board near the overhead door were removed and not effectively closed. b. Site- Employees were not protected from electric shock and burns where unused openings for circuit breakers in the panel board near the overhead door were not covered and live parts were exposed.