Violation Detail
Standard Cited: 19100303 F02 General.
Inspection Nr: 1452387.015
Citation: 01007C
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $5,725.00
Current Penalty: $0.00
Issuance Date: 05/07/2020
Nr Instances: 3
Nr Exposed: 45
Abatement Date:
Gravity: 1
Report ID: 0524500
Contest Date:
Final Order: 05/20/2020
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 05/20/2020 | $0.00 | Serious | ||
| Penalty | Z: Issued | 05/07/2020 | $5,725.00 | Serious |
Text For Citation: 01 Item/Group: 007C Hazard:
29 CFR 1910.303(f)(2): Each service, feeder, and branch circuit, at its disconnecting means or overcurrent device, was not legibly marked to indicate its purpose, nor located and arranged so the purpose was evident: On or about December 17, 2019, Northside of the shop, North wall, employees were exposed to electrical shock hazards and the employer did not label the branch circuits in the Square D panel with their purpose.