Violation Detail
Standard Cited: 19100307 C02 I Hazardous (classified) locations.
Inspection Nr: 1742763.015
Citation: 01007B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 09/27/2024
Nr Instances: 1
Nr Exposed: 23
Abatement Date: 01/31/2025
Gravity: 10
Report ID: 0523900
Contest Date:
Final Order: 10/25/2024
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 10/25/2024 | $0.00 | 01/31/2025 | Serious | |
Penalty | Z: Issued | 09/27/2024 | $0.00 | 11/19/2024 | Serious |
Text For Citation: 01 Item/Group: 007B Hazard:
29 CFR 1910.307(c)(2)(i): Equipment in hazardous (classified) location(s) was not approved for the ignitable or combustible properties of the specific gas, vapor, dust, or fiber that was or could be present: (a) South Plant - Bulk House, 2nd Floor; On or about April 19, 2024, equipment including, but not limited to, the Baldor Reliance motor(s) and associated drive systems were not dust-tight and were not approved for a Class II Division 2 hazardous location, where the bulk loading of Class II combustible grain dust was performed.