Violation Detail
Standard Cited: 19100303 G01 I A General.
Inspection Nr: 1696385.015
Citation: 01007B
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 12/05/2023
Nr Instances: 1
Nr Exposed: 10
Abatement Date:
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 01/12/2024
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 01/12/2024 | $0.00 | Serious | ||
| Penalty | Z: Issued | 12/05/2023 | $0.00 | Serious |
Text For Citation: 01 Item/Group: 007B Hazard:
29 CFR 1910.303(g)(1)(i)(A): For electric equipment operating at 600 volts, nominal, or less to ground, and likely to require examination, adjustment, servicing, or maintenance while energized, the depth of the working space in the direction of access to live parts (as measured from the live parts where they were exposed or from the enclosure front or opening where they were enclosed) was less than indicated in Table S-1 of Subpart S of Part 1910: Break Room: On, or about, September 8, 2023, the lunch table was located within the working space for the Federal Pacific electrical enclosure. The panel was 480 volts and contained the main service entrance.