Violation Detail
Standard Cited: 19100307 C01 Hazardous (classified) locations.
Inspection Nr: 1612138.015
Citation: 01007B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/20/2023
Nr Instances: 2
Nr Exposed: 36
Abatement Date: 07/31/2025
Gravity: 5
Report ID: 0112600
Contest Date:
Final Order: 02/13/2023
Related Event Code (REC):
Emphasis:
Substance: 1660
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | P: Petition to Mod Abatement | 12/17/2024 | $0.00 | 07/31/2025 | Serious | |
Penalty | P: Petition to Mod Abatement | 08/02/2024 | $0.00 | 12/31/2024 | Serious | |
Penalty | P: Petition to Mod Abatement | 05/31/2024 | $0.00 | 12/31/2024 | Serious | |
Penalty | P: Petition to Mod Abatement | 03/29/2024 | $0.00 | 12/31/2024 | Serious | |
Penalty | P: Petition to Mod Abatement | 10/13/2023 | $0.00 | 04/01/2024 | Serious | |
Penalty | I: Informal Settlement | 02/13/2023 | $0.00 | 10/13/2023 | Serious | |
Penalty | Z: Issued | 01/20/2023 | $0.00 | 03/09/2023 | Serious |
Text For Citation: 01 Item/Group: 007B Hazard:
29 CFR 1910.307(c)(1): Equipment and associated wiring not approved as intrinsically safe was permitted in a hazardous location (Classified) location for which it was not approved: 165 Pioneer Dr, Leominster MA: Filling area: (a) On or about 8/3/22, electrical equipment such as, but not limited to, a floor fan not approved as intrinsically safe for use in a hazardous (classified)location was used in an area the employer had classified as Class 1, Division 1. Area adjacent to blend-on-demand (BOD) room: (b) On or about 8/3/22, electrical equipment such as, but not limited to, electrical panels, junction boxes, and outlets not approved as intrinsically safe for use in a hazardous (classified) location was used in an area the employer had classified as Class 1, Division 2.