Violation Detail
Standard Cited: 19100304 F01 VIII Wiring design and protection.
Inspection Nr: 1573945.015
Citation: 01007B
Citation Type: Serious
Abatement Date: 07/26/2022 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/29/2022
Nr Instances: 1
Nr Exposed: 10
Related Event Code (REC):
Gravity: 5
Report ID: 0316700
Contest Date:
Final Order: 09/08/2022
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/08/2022 | $0.00 | 07/26/2022 | Serious | |
Penalty | Z: Issued | 06/29/2022 | $0.00 | 07/26/2022 | Serious |
Text For Citation: 01 Item/Group: 007B Hazard:
29 CFR 1910.304(f)(1)(viii):The employer shall ensure that all circuit breakers used as switches are labeled "SWD". a. Panel P-4 - On or about February 28, 2022, the breakers 1-6 are for lights that are turned on and off every day but are not designated as SWD, exposing employees to an electrical hazard. Abatement certification required within 10 days after abatement date. The certification shall include a statement that abatement is complete, date and method of abatement, and states employees and their representatives were informed of this abatement.