Violation Detail
Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1443494.015
Citation: 01007B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 03/16/2020
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 07/31/2020
Gravity: 5
Report ID: 0521100
Contest Date:
Final Order: 04/09/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | P: Petition to Mod Abatement | 05/06/2020 | $0.00 | 07/31/2020 | Serious | |
Penalty | I: Informal Settlement | 04/09/2020 | $0.00 | 05/08/2020 | Serious | |
Penalty | Z: Issued | 03/16/2020 | $0.00 | 05/04/2020 | Serious |
Text For Citation: 01 Item/Group: 007B Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables shall be connected to devices and fittings so that strain relief is provided that will prevent pull from being directly transmitted to joints or terminal screws. a) The cord and plug that power 110 Ac Volt electric to the overhead lighting located in the Maintenance Shop had damage and the strain relief was pulled out of the plug fitting exposing wire conductor. b) The 480 AC Volt electric wiring to the McDonough Re-Saw electric motor was pulled out from the strain relief exposing three wire conductors.