Violation Detail
Standard Cited: 19100107 E01 Spray finishing using flammable and combustible materials.
Inspection Nr: 1466507.015
Citation: 01007A
Citation Type: Serious
Abatement Date: 10/19/2020 2
Initial Penalty: $4,048.00
Current Penalty: $1,590.00
Issuance Date: 08/31/2020
Nr Instances: 1
Nr Exposed: 2
Related Event Code (REC): C
Gravity: 1
Report ID: 0112000
Contest Date:
Final Order: 09/28/2020
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/28/2020 | $1,590.00 | 10/19/2020 | Serious | |
Penalty | Z: Issued | 08/31/2020 | $4,048.00 | 10/19/2020 | Serious |
Text For Citation: 01 Item/Group: 007A Hazard:
29 CFR 1910.107(e)(1): The employer did not ensure that the storage of flammable liquids in connection with spraying operations conformed to the requirements of 29 CFR 1910.106, including paragraph (e)(2)(iv)(C). ADHESIVE SPRAY AREA: On or about and at times prior to March 2, 2020, a small, uncovered plastic pail containing a Category 2 flammable adhesive was stored under the work bench. The adhesive was 3M PB938 High Performance Spray Adhesive with a flashpoint of -4 deg F and a boiling point of 133 deg F. Ref. 29 CFR 1910.106(e)(2)(iv)(a)