Standard Cited: 19100305 B01 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1435913.015
Citation: 01007A
Citation Type: Serious
Abatement Date: 02/21/2020 2
Initial Penalty: $10,229.00
Current Penalty: $6,819.00
Issuance Date: 01/03/2020
Nr Instances: 3
Nr Exposed: 4
Related Event Code (REC):
Gravity: 5
Report ID: 0936200
Contest Date: 02/13/2020
Final Order: 03/24/2021
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 03/24/2021 | $6,819.00 | 02/21/2020 | Serious | |
Penalty | C: Contested | 02/18/2020 | $10,229.00 | 02/21/2020 | Serious | |
Penalty | Z: Issued | 01/03/2020 | $10,229.00 | 02/21/2020 | Serious |
Text For Citation: 01 Item/Group: 007A Hazard:
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed. Building 1327, North Storage room: The HVAC unit on the North wall had round sharp cutouts from the aluminum housing which had electrical wiring passing through and was not effectively closed. Employees were exposed to electrical hazards.