Violation Detail
Standard Cited: 19100125 E02
Inspection Nr: 1368252.015
Citation: 01007A
Citation Type: Serious
Abatement Date: 01/10/2020 2
Initial Penalty: $13,260.00
Current Penalty: $10,760.00
Issuance Date: 06/11/2019
Nr Instances: 1
Nr Exposed: 139
Related Event Code (REC):
Gravity: 10
Report ID: 0522300
Contest Date: 06/13/2019
Final Order: 01/03/2020
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 01/03/2020 | $10,760.00 | 01/10/2020 | Serious | |
Penalty | C: Contested | 07/11/2019 | $13,260.00 | 07/01/2019 | Serious | |
Penalty | Z: Issued | 06/11/2019 | $13,260.00 | 07/01/2019 | Serious |
Text For Citation: 01 Item/Group: 007A Hazard:
29 CFR 1910.125(e)(2): Portable container(s) used to add liquid to the tank was not electrically bonded to the dip tank and was not positively grounded to prevent static electrical sparks or arcs: On or about December 27, 2018, the employer failed to ensure that the portable container used to add Water Reducible Alkyd Dip Enamel, a Category 3 flammable liquid, to the dip dank was electrically bonded to the dip tank to electrostatic spark.