Violation Detail
Standard Cited: 19100305 B01 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1288984.015
Citation: 01007A
Citation Type: Serious
Abatement Status: Corrected During Inspection
Initial Penalty: $8,315.00
Current Penalty: $8,315.00
Issuance Date: 07/02/2018
Nr Instances: 3
Nr Exposed: 4
Abatement Date:
Gravity: 5
Report ID: 0419700
Contest Date: 07/24/2018
Final Order: 05/17/2019
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 05/17/2019 | $8,315.00 | Serious | ||
Penalty | C: Contested | 07/30/2018 | $8,315.00 | Serious | ||
Penalty | Z: Issued | 07/02/2018 | $8,315.00 | Serious |
Text For Citation: 01 Item/Group: 007A Hazard:
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasions: a. On or about January 21, 2018, in the pipe shop along the west wall, the conductor entering the panel box supplying power to the welder was not protected from abrasions, exposing employees to an electrical shock hazard. b. On or about January 21, 2018, on the south side of the fabrication shop, the conductor entering the panel box supplying power to the welder was not protected from abrasions, exposing employees to an electrical shock hazard. c. On or about January 21, 2018, in the middle of the fabrication shop, the conductor entering the panel box supplying power to the welder was not protected from abrasions, exposing employees to an electrical shock hazard.