Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 984505.015
Citation: 01007
Citation Type: Serious
Abatement Status: Not Completed - Employer Out of Business
Initial Penalty: $3,080.00
Current Penalty: $1,000.00
Issuance Date: 01/06/2015
Nr Instances: 3
Nr Exposed: 8
Abatement Date: 02/24/2015
Gravity: 5
Report ID: 0112000
Contest Date: 07/06/2020
Final Order: 07/06/2020
Related Event Code (REC):
Emphasis:
Failure to Abate | |||||||
---|---|---|---|---|---|---|---|
Activity Nr | Issuance | Penalty | Contest | Final Order | |||
1161632 | 05/09/2016 | $4,030.76 | 07/06/2020 | 07/06/2020 |
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
FTA | C: Contested | 07/30/2020 | $16,000.00 | 06/11/2016 | 1161632.015 | |
Penalty | C: Contested | 07/30/2020 | $3,080.00 | 02/24/2015 | Serious | |
FTA | F: Formal Settlement | 07/06/2020 | $4,030.76 | 06/11/2016 | 1161632.015 | |
Penalty | F: Formal Settlement | 07/06/2020 | $1,000.00 | 02/24/2015 | Serious | |
FTA | Z: Issued | 05/09/2016 | $16,000.00 | 06/11/2016 | 1161632.015 | |
Penalty | Z: Issued | 01/06/2015 | $3,080.00 | 02/24/2015 | Serious |
Text For Citation: 01 Item/Group: 007 Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: In the following locations, electrical equipment was improperly used or installed: A) WELDING AREA NEAR OFFICE: On or about July 22, 2014, a Hevi-Duty transformer that was installed between the overhead buss bar and Panel RP22, a 120/208 circuit breaker panel, was installed with conduit entering the top of the transformer enclosure instead of using the opening provided by the manufacturer. B) OFFICE AREA: On or about July 10, 2014, a GE refrigerator was energized by a relocatable power tap mounted to the wall. C) OFFICE AREA: On or about July 10, 2014, three relocatable power taps were connected in series. Each was also used to energize computer and telephone peripherals.