Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.

Inspection Nr: 314505298

Citation: 01007

Citation Type: Serious

Abatement Status: X

Initial Penalty: $2,000.00

Current Penalty: $2,000.00

Issuance Date: 11/09/2010

Nr Instances: 1

Nr Exposed: 23

Abatement Date: 12/03/2010

Gravity: 10

Report ID: 0729300

Contest Date:

Final Order:

Related Event Code (REC):

Emphasis:



Text For Citation: 01 Item/Group: 007 Hazard: CHEMNEP

29 CFR 1910.119(d)(3)(ii): The employer did not document that the equipment in the process complied with recognized and generally accepted good engineering practices: The employer did not document the following RAGAGEP were followed: a. Where flammable chemicals such as acetone, ethyl ether, toluene and isopropyl alcohol were used as base product, mechanical exhaust ventilation was not installed at the filling station.(NFPA 30B 4.4.3, 2007 Edition) b. The aerosol container test bath was not enclosed and equipped with exhaust ventilation.(NFPA 30B 5.4.4, 2007 Edition) c. Where chemicals were likely to spill on the floor of the base chemical filling line, drainage systems were not provided to direct the leaks in to a safe location (NFPA 30B 5.10.1, 2007 Edition). Abatement certification and abatement documentation is required for this violation. The documentation should include written verification of abatement, applicable measurements or monitoring results, and photographs or videos which you believe will be helpful. The abatement certification sheet is enclosed with the citation(s).

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close