Violation Detail
Standard Cited: 19100119 J02 Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 313137804
Citation: 01007
Citation Type: Serious
Abatement Status:
Initial Penalty: $7,000.00
Current Penalty:
Issuance Date: 09/14/2011
Nr Instances: 4
Nr Exposed: 500
Abatement Date: 09/27/2011
Gravity: 10
Report ID: 0523300
Contest Date:
Final Order:
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 09/28/2011 | 09/27/2011 | Serious | ||
| Penalty | Z: Issued | 09/14/2011 | $7,000.00 | 09/27/2011 | Serious |
Text For Citation: 01 Item/Group: 007 Hazard: CHEMNEP
29 CFR 1910.119(j)(2): The employer did not establish and implement written procedures to maintain the on-going mechanical integrity of process equipment: The employer did not establish written procedures to maintain the on-going mechanical integrity of the ammonia refrigeration system. a) Inspection, maintaining and replacing relief devices. b) Inspection and testing on the Vilter compressor safety cutout switches. ABATEMENT DOCUMENTATION REQUIRED PER 29 CFR 1903.19(d)ION