Violation Detail
Standard Cited: 19100106 C06 Flammable liquids.
Inspection Nr: 1776083.015
Citation: 01007
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $6,620.00
Current Penalty: $6,620.00
Issuance Date: 03/05/2025
Nr Instances: 1
Nr Exposed: 1
Abatement Date: 04/21/2025
Gravity: 5
Report ID: 1032500
Contest Date: 03/31/2025
Final Order: 06/20/2025
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 06/20/2025 | $6,620.00 | 04/21/2025 | Serious | |
Penalty | C: Contested | 04/10/2025 | $6,620.00 | 04/21/2025 | Serious | |
Penalty | Z: Issued | 03/05/2025 | $6,620.00 | 04/21/2025 | Serious |
Text For Citation: 01 Item/Group: 007 Hazard:
1910.106(c)(6): Each connection to pipelines, by which equipments such as tankcars or tank vehicles discharge liquids by means of pumps into storage tanks, were not provided with a check valve for automatic protection against backflow if the piping arrangement is such that backflow from the system is possible. a) On September 11, 2024, and at times prior thereto, employees pumped fuel into storage tanks without a check valve located on the receipt line. Note: Certification of corrective action is required for this item.