Violation Detail
Standard Cited: 19100304 G05 Wiring design and protection.
Inspection Nr: 1434719.015
Citation: 01007
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,783.00
Current Penalty: $4,048.10
Issuance Date: 03/20/2020
Nr Instances: 1
Nr Exposed: 7
Abatement Date: 04/10/2020
Gravity: 1
Report ID: 0729300
Contest Date:
Final Order: 04/02/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/02/2020 | $4,048.10 | 04/10/2020 | Serious | |
Penalty | Z: Issued | 03/20/2020 | $5,783.00 | 04/10/2020 | Serious |
Text For Citation: 01 Item/Group: 007 Hazard:
29 CFR 1910.304(g)(5): The path to ground from circuits, equipment, and enclosures was not permanent, continuous, and effective: The employer is failing to prevent employee exposure to electrical hazards. On or about October 1, 2019, equipment grounding conductor (ground pin) to a 110 V cooling fan at the north kettle was missing. Abatement documentation is required for this violation.