Violation Detail
Standard Cited: 19100107 E09 Spray finishing using flammable and combustible materials.
Inspection Nr: 1405431.015
Citation: 01007
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,978.00
Current Penalty: $1,472.00
Issuance Date: 12/02/2019
Nr Instances: 2
Nr Exposed: 4
Abatement Date: 12/30/2019
Gravity: 10
Report ID: 0524530
Contest Date: 12/18/2019
Final Order: 08/17/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 08/17/2020 | $1,472.00 | 12/30/2019 | Serious | |
Penalty | C: Contested | 12/20/2019 | $3,978.00 | 12/30/2019 | Serious | |
Penalty | Z: Issued | 12/02/2019 | $3,978.00 | 12/30/2019 | Serious |
Text For Citation: 01 Item/Group: 007 Hazard:
29 CFR 1910.107(e)(9): Flammable liquids for use in spraying operations were transferred from one container to another without both containers being effectively bonded and grounded to prevent discharge sparks of static electricity: The employer failed to ensure that flammable liquids were dispensed into containers that were ground and bonded when: A. Pioneer 68 Asphalt Paint, a Category 1 flammable liquid with a flashpoint of fifty (50) degrees was dispensed from a metal fifty-five (55) gallon drum into a plastic coffee container and no grounding or bonding device was used. B. Quick Dry Bronzing Fluid, a Category 1 flammable liquid with a flashpoint of fifty (50) degrees was dispensed from a metal fifty-five (55) gallon drum into a plastic coffee container and no bonding device was used.