Violation Detail
Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1399364.015
Citation: 01007
Citation Type: Serious
Abatement Status: Not Completed - Employer Out of Business
Initial Penalty: $3,031.00
Current Penalty: $0.00
Issuance Date: 09/16/2019
Nr Instances: 1
Nr Exposed: 9
Abatement Date: 10/01/2019
Gravity: 5
Report ID: 0524500
Contest Date: 10/10/2019
Final Order: 03/04/2020
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | R: Review Commission | 03/04/2020 | $0.00 | 10/01/2019 | Serious | |
Penalty | C: Contested | 10/16/2019 | $3,031.00 | 10/01/2019 | Serious | |
Penalty | Z: Issued | 09/16/2019 | $3,031.00 | 10/01/2019 | Serious |
Text For Citation: 01 Item/Group: 007 Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords and cables were not connected to devices and fittings so that strain relief was provided that would prevent pull from being directly transmitted to joints or terminal screws: On or about May 8, 2019 employees were exposed to the hazard of electrical shock when working in and around the hallway of Gestation Room 1 because the flexible power cord providing power to the hallway lighting was not connected to the light fixture with devices and fittings that would have prevented tension from being transmitted to the flexible cords.