Violation Detail
Standard Cited: 19100305 G02 III Wiring methods, components, and equipment for general use.
Inspection Nr: 1228656.015
Citation: 01007
Citation Type: Serious
Abatement Date: 09/25/2017 2
Initial Penalty: $4,155.00
Current Penalty: $2,493.00
Issuance Date: 08/29/2017
Nr Instances: 1
Nr Exposed: 5
Related Event Code (REC): C
Gravity: 1
Report ID: 0418100
Contest Date:
Final Order: 09/22/2017
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 09/22/2017 | $2,493.00 | 09/25/2017 | Serious | |
Penalty | Z: Issued | 08/29/2017 | $4,155.00 | 09/25/2017 | Serious |
Text For Citation: 01 Item/Group: 007 Hazard:
29 CFR 1910.305(g)(2)(iii): Flexible cords were not connected to devices and fittings so that tension would not be transmitted to joints or terminal screws: a) Foam gun department - On or about April 21,2017, employees used a control panel, to control the temperature of the hose. An extension cord was hard wired to the control panel. Strain relief was not provided where the cord was connected to the control panel; the insulated conductors were exposed. In accordance with 29 CFR 1903.19(c), abatement certification is required for this violation (using the CERTIFICATION OF CORRECTIVE ACTION WORKSHEET).