Violation Detail
Standard Cited: 19100253 B04 III Oxygen-fuel gas welding and cutting.
Inspection Nr: 1211861.015
Citation: 01007
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,243.00
Current Penalty: $4,375.00
Issuance Date: 08/16/2017
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 08/31/2017
Gravity: 5
Report ID: 0214200
Contest Date: 09/08/2017
Final Order: 03/08/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 03/08/2018 | $4,375.00 | 08/31/2017 | Serious | |
Penalty | C: Contested | 10/13/2017 | $7,243.00 | 08/31/2017 | Serious | |
Penalty | Z: Issued | 08/16/2017 | $7,243.00 | 08/31/2017 | Serious |
Text For Citation: 01 Item/Group: 007 Hazard:
29 CFR 1910.253(b)(4)(iii): Oxygen cylinders in storage were not separated from fuel-gas cylinders or combustible materials (especially oil or grease), a minimum distance of 20 feet (6.1 m) or by a noncombustible barrier at least 5 feet (1.5 m) high having a fire-resistance rating of at least one half hour: a) Maintenance shop An oxygen cylinder was stored immediately next to an acetylene cylinder exposing employees to fire hazards. The cylinders were not separated by a noncombustible barrier or at least 20 feet apart. Violation observed on or about 02/21/2017.