Violation Detail
Standard Cited: 19100024 G Step bolts and manhole steps.
Inspection Nr: 1135323.015
Citation: 01007
Citation Type: Serious
Abatement Status: Not Completed - Worksite Changed
Initial Penalty: $8,017.00
Current Penalty: $7,445.15
Issuance Date: 09/22/2016
Nr Instances: 1
Nr Exposed: 4
Abatement Date: 11/14/2016
Gravity: 5
Report ID: 0111400
Contest Date:
Final Order: 10/17/2016
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/17/2016 | $7,445.15 | 11/14/2016 | Serious | |
| Penalty | Z: Issued | 09/22/2016 | $8,017.00 | 11/14/2016 | Serious |
Text For Citation: 01 Item/Group: 007 Hazard:
29 CFR 1910.24(g): Stairway platforms were less than 30 inches in length measured in the direction of travel: Stairway Platform in Ammonia Machinery Room: Employees were exposed to fall hazards while walking up and down the stairs where the upper landing measured approximately 24-inches, and where a fixed ladder on the same landing further restricted the length of the platform to 12.5-inches