Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1014030.015
Citation: 01007
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,000.00
Current Penalty: $2,400.00
Issuance Date: 01/15/2015
Nr Instances: 14
Nr Exposed: 7
Abatement Date: 01/28/2015
Gravity: 1
Report ID: 0111100
Contest Date:
Final Order: 02/10/2015
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 02/10/2015 | $2,400.00 | 01/28/2015 | Serious | |
| Penalty | Z: Issued | 01/15/2015 | $3,000.00 | 01/28/2015 | Serious |
Text For Citation: 01 Item/Group: 007 Hazard:
29 CFR 1910.303(b)(2): Listed or labeled equipment were not installed and used in accordance with any instructions included in the listing or labeling. In the following instances, portable powered tools were not used according to its listing or labeling: a) Repair Station #11 - The plug attached to the double insulated Bosch reciprocating saw was modified to a 120 volt three wire twist lock plug. In addition, the rubber boot was missing, exposing the metal frame which had 26 volts to ground. b) Repair Station #12 - The plug attached to the double insulated Bosch reciprocating saw was modified to a 120 volt three wire twist lock plug. In addition, the rubber boot separated and exposed a portion of the metal frame which had 28 volts to ground. c) Repair Station #3 - The plug attached to each double insulated SENCO screwdriver gun was modified to a 120 volt three wire twist lock plug. In addition, the gun's metal feed housing had 29 volts to ground. d) Repair Station #5 - The plug attached to each double insulated SENCO screwdriver gun was modified to a 120 volt three wire twist lock plug. In addition, the gun's metal feed housing had 12-25 volts to ground. e) Repair Station #6 - The plug attached to each double insulated SENCO screwdriver gun was modified to a 120 volt three wire twist lock plug. In addition, the gun's metal feed housing had 30 volts to ground. f) Repair Station #8 - The plug attached to each double insulated SENCO screwdriver gun was modified to a 120 volt three wire twist lock plug. In addition, the gun's metal feed housing had 4 volts to ground. g) Repair Station #9 - The plug attached to each double insulated SENCO screwdriver gun was modified to a 120 volt three wire twist lock plug. In addition, the 2 week old gun's metal feed housing had 9 volts to ground.
Translate