Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100307 C Hazardous (classified) locations.

Inspection Nr: 947859.015

Citation: 01006C

Citation Type: Serious

Abatement Status: Not Completed - Worksite Changed

Initial Penalty: $0.00

Current Penalty: $0.00

Issuance Date: 05/01/2014

Nr Instances: 12

Nr Exposed: 1

Abatement Date: 06/18/2014

Gravity: 10

Report ID: 0134000

Contest Date: 05/27/2014

Final Order: 07/11/2014

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty W: Empr Withdrew 07/11/2014 $0.00 06/18/2014 Serious  
Penalty C: Contested 06/27/2014 $0.00 06/18/2014 Serious  
Penalty Z: Issued 05/01/2014 $0.00 06/18/2014 Serious  

Text For Citation: 01 Item/Group: 006C Hazard:

29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location On or about 11/5/13, the employer had Class II, Division 1 hazardous locations with standard electrical installations, pieces of equipment, and wiring methods that were neither approved nor safe for those locations and were not intrinsically safe: A. CONCEPT Laser GmbH M2 Cusing, Serial No. M2-2013-02-01 [3D Printer] B. TBH GmbH FP 150 EX II 3D De-Duster, attached and adjacent to 3D Printer Serial No. M2-2013-02-01 C. Rofin-Baasel Lasertech GmbH & Co KG 400 watt Fiber Laser, attached and adjacent to 3D Printer SN M2-2013-02-01 D. CONCEPT Laser M2 Cusing GmbH, Serial No. M2-2012-03-04 [3D Printer]) E. TBH GmbH FP 150 EX II 3D De-Duster, attached and adjacent to 3D Printer Serial No. M2-2012-03-04 F. Rofin-Baasel Lasertech GmbH & Co KG 400 watt Fiber Laser, attached and adjacent to 3D Printer Serial No. M2- 2012-03-04 G. CONCEPT Laser QM Powder with Italvibras S.p.A. Electric Vibrator MTF 15 [Sieving station] H. Ruwac Industriesauger GmbH NA 35 Wet Separator [Vacuum] I. Ridgid shop vacuum Serial No 08006 R 2314. J. Electrical panels, boxes, receptacles, light switches, and premises wiring behind and adjacent to the two CONCEPT Laser GmbH M2 Cusing 3D Printers, including the receptacle used to power the Ruwac Industriesauger GmbH Wet Separator K. Electrical panels, boxes, receptacles, light switches, and premises wiring behind and adjacent to the CONCEPT Laser QM Powder with Italvibras S.p.A. Electric Vibrator MTF 15 [Sieving station], including the receptacle used to power the Ruwac Industriesauger GmbH Wet Separator

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.