Violation Detail
Standard Cited: 19100119 F01 IV Process safety management of highly hazardous chemicals.
Inspection Nr: 329260.015
Citation: 01006C
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $5,000.00
Current Penalty: $0.00
Issuance Date: 09/18/2012
Nr Instances: 7
Nr Exposed: 78
Abatement Date: 10/02/2012
Gravity: 5
Report ID: 0625700
Contest Date:
Final Order: 10/08/2012
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/08/2012 | $0.00 | 10/02/2012 | Serious | |
| Penalty | Z: Issued | 09/18/2012 | $5,000.00 | 10/02/2012 | Serious |
Text For Citation: 01 Item/Group: 006C Hazard:
29 CFR 1910.119(f)(1)(iv): The employer did not develop and implement written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information and which addressed safety systems and their function: In Area 1 of the VCM unit: The employer did not develop or implement operating procedures for the administrative control of car seals/mechanical locking elements on intervening stop valves in the upstream and downstream lines to/from the following pressure relief devices (PRDs) to ensure they remained in the open position during operation: 1. PSV-E7101A-D, PSE-E7101A-C; 2. PSV-E7106A-A; 3. PSV-T7103A-A, PSE- T7103A-A, PSV-T7103A-B, PSE- T7103A-B; 4. PSV-V7108A-A, PSE-V7108A-A; 5. PSV-E7102B-C, PSE-E7102B-C; 6. PSE-V7105A-A; 7. PSE-V7106A-A. This violation was documented on or about 03/22/2012.