Standard Cited: 19100303 B02 General.

Inspection Nr: 947859.015

Citation: 01006B

Citation Type: Serious

Abatement Status: Not Completed - Worksite Changed

Initial Penalty: $0.00

Current Penalty: $0.00

Issuance Date: 05/01/2014

Nr Instances: 10

Nr Exposed: 1

Abatement Date: 07/10/2014

Gravity: 10

Report ID: 0134000

Contest Date: 05/27/2014

Final Order: 07/11/2014

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty W: Empr Withdrew 07/11/2014 $0.00 07/10/2014 Serious  
Penalty C: Contested 06/27/2014 $0.00 07/10/2014 Serious  
Penalty Z: Issued 05/01/2014 $0.00 07/10/2014 Serious  

Text For Citation: 01 Item/Group: 006B Hazard:

29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about 11/5/13, the following pieces of the employer's CONCEPT Laser 3D printing system were not used or installed in accordance with the instructions included in the listing or labeling: 1. CONCEPT Laser GmbH M2 Cusing, Serial No. M2-2013-02-01 [3D Printer] 2. TBH GmbH FP 150 EX II 3D De-Duster, attached and adjacent to 3D Printer Serial No. M2-2013-02-01 3. Rofin-Baasel Lasertech GmbH & Co KG 400 watt Fiber Laser, attached and adjacent to 3D Printer SN M2-2013-02-01 4. CONCEPT Laser M2 Cusing GmbH, Serial No. M2-2012-03-04 [3D Printer]) 5. TBH GmbH FP 150 EX II 3D De-Duster, attached and adjacent to 3D Printer Serial No. M2-2012-03-04 6. Rofin-Baasel Lasertech GmbH & Co KG 400 watt Fiber Laser, attached and adjacent to 3D Printer Serial No. M2- 2012-03-04 7. CONCEPT Laser QM Powder with Italvibras S.p.A. Electric Vibrator MTF 15 [Sieving station] 8. Ruwac Industriesauger GmbH NA 35 Wet Separator [Vacuum] 9. Ridgid shop vacuum Serial No 08006 R 2314. Employee used an ordinary Ridgid shop vacuum to collect fugitive combustible metal shavings, dust and powder from the floor, surfaces and machinery. The Ridgid was not rated for use with combustible dust.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.