Violation Detail
Standard Cited: 19100119 D03 I D Process safety management of highly hazardous chemicals.
Inspection Nr: 941314.015
Citation: 01006B
Citation Type: Serious
Abatement Date: 06/02/2014 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 03/07/2014
Nr Instances: 1
Nr Exposed: 6
Related Event Code (REC):
Gravity: 1
Report ID: 0418100
Contest Date:
Final Order: 03/27/2014
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/27/2014 | $0.00 | 06/02/2014 | Serious | |
Penalty | Z: Issued | 03/07/2014 | $0.00 | 04/23/2014 | Serious |
Text For Citation: 01 Item/Group: 006B Hazard:
29 CFR 1910.119(d)(3)(i)(D): The employer did not maintain an accurate listing of the location, function, and inspection information for all Relief Valves (RV) within a covered process. On or about 9/11/13, at the 1 Lemon Lane, Atlanta Ga Schwan facility, the employer did not maintain information pertaining to relief valves for the ammonia refrigeration system on site, such as the relief system design and design basis. In accordance with 29 CFR 1903.19(d), abatement certification is required for this violation (using the CERTIFICATION OF ACTION WORKSHEET), and in addition, documentation demonstrating that abatement is complete must be included with your certification. This documentation may include, but is not limited to, evidence of the purchase or repair of the equipment, photographic or video evidence of abatement, or other written records.