Powered by GoogleTranslate

Violation Detail

Standard Cited: 19100119 F01 Process safety management of highly hazardous chemicals.

Inspection Nr: 312602147

Citation: 01006B

Citation Type: Serious

Abatement Status: X

Initial Penalty:

Current Penalty:

Issuance Date: 09/30/2009

Nr Instances: 4

Nr Exposed: 113

Abatement Date: 06/30/2010

Gravity: 10

Report ID: 0627400

Contest Date: 10/23/2009

Final Order: 04/16/2010

Related Event Code (REC):

Emphasis:


Penalty and Failure to Abate Event History
Type Latest Event Event Date Penalty Abatement Due Date Citation Type Failure to Abate Inspection
Penalty J: ALJ Decision 04/16/2010 06/30/2010 Serious  
Penalty Z: Issued 09/30/2009 02/12/2010 Serious  

Text For Citation: 01 Item/Group: 006B Hazard: REFINERY

29 CFR 1910.119(f)(1): The employer had not developed and implemented written operating procedures that provided clear instructions for safely conducting activities involved in each covered process consistent with the process safety information: ALON USA, LP, 200 Refinery Road, Big Spring, TX. The employer does not implement its car seal program which requires that Operations Coordinators conduct inspections to ensure that pressure relief valves / gate valves have car seals or other positive locking devices in place when a pressure vessel is the possible source of a relieving event or when it utilizes some component of the relief system which does not meet RAGAGEP design requirements. This violation was observed on or about April 15, 2009 in the following instances: a) The Operations Coordinators failed to identify that car seals or other positive locking devices were present on several pressure relief valves in the #1 SCOT Unit (068RV-416, 068RV-422, 068RV-423 and 068RV-420), #2 SCOT Unit (72RV-909 and 72RV-904) and Sour Water Stripper (074RV-423) had no car seals or positive locking devices installed on valves located on the downstream side of these relief valves. These valves could conceivably be closed in the event of a relieving event, thus compromising the effectiveness of the relief devices. b) The Operations Coordinators failed to identify that car seals or other positive locking devices were present on a gate valve located in a flare line (FLR-209A-A) feeding the Northside flare knockout drum did not have a car seal or positive locking device mounted on it. This flare line, which provided flare service to the Aromex and Rexformer Units, could thus conceivably be closed in the event of a relieving event, thus compromising the effectiveness of the relief devices. c) The Operations Coordinators failed to identify that car seals or other positive locking devices were present on a gate valve located in a flare line (FLR-209A-A) feeding the Northside Flare Knockout Drum did not have a car seal or positive locking device mounted on it. A positive locking device that was on this valve on April 22, 2009 had been removed and placed on an adjacent gate valve that was not secured on April 22, 2009. This flare line, which provided flare service to the #1 SCOT and Diesel Hydrotreater Units, could thus conceivably be closed in the event of a relieving event, thus compromising the effectiveness of the relief devices. d) The Operations Coordinators failed to identify that car seals or other positive locking devices were present on a gate valve mounted in the flare line from the #1 SCOT Unit (FLR-068-184- FA4A2) where it met the flare line from the Diesel Hydrotreater (FLR-014-117-FA4A2), did not have a car seal or positive locking device mounted on it. This flare line, which provided service to the #1 SCOT Unit, could thus conceivably be closed in the event of a relieving event, thus compromising the effectiveness of the relief devices. Pursuant to 29 C.F.R. 1903.19, within ten (10) calendar days of the date of this citation, the employer must submit documentation showing that it is in compliance with the standard, including describing the steps that it is taking in the workplace to ensure that inspections are conducted and documented that pressure relief valves / gate valves have car seals or other positive locking devices.

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close