Violation Detail
Standard Cited: 19100303 G02 I General.
Inspection Nr: 1651629.015
Citation: 01006B
Citation Type: Serious
Abatement Date: 07/10/2023 2
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 05/19/2023
Nr Instances: 1
Nr Exposed: 4
Related Event Code (REC):
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 07/06/2023
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/06/2023 | $0.00 | 07/10/2023 | Serious | |
Penalty | Z: Issued | 05/19/2023 | $0.00 | 07/10/2023 | Serious |
Text For Citation: 01 Item/Group: 006B Hazard:
29 CFR 1910.303(g)(2)(i): Except as elsewhere required or permitted by Subpart S of Part 1910, live parts of electric equipment operating at 50 volts or more were not guarded against accidental contact by use of approved cabinets or other forms of approved enclosures or by any of the means identified in paragraphs (A), (B), (C), and (D) of 29 CFR 1910.303(g)(2)(i): Basement, Electrical Cage: On, or about, February 22, 2023, the switchboard enclosure for the main 240 volt switchgear was not provided with non-combustible, rear panels. Some wooden panels were installed and some panels were left off, exposing the inner buss bars and connections.