Violation Detail
Standard Cited: 19100119 J04 I Process safety management of highly hazardous chemicals.
Inspection Nr: 1455632.015
Citation: 01006B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 06/26/2020
Nr Instances: 13
Nr Exposed: 2
Abatement Date: 07/16/2020
Gravity: 10
Report ID: 0626300
Contest Date:
Final Order: 07/23/2020
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/23/2020 | $0.00 | 07/16/2020 | Serious | |
Penalty | Z: Issued | 06/26/2020 | $0.00 | 07/16/2020 | Serious |
Text For Citation: 01 Item/Group: 006B Hazard:
29 CFR 1910.119(j)(4)(i): The employer did not perform inspection and tests on process equipment a) On or about January 13, 2020, the employer did not perform inspections and testing on process equipment, including pressure relief valves such as, but not limited to: 1. Deethanizer PSV-1100, 2. Propane Tank PSV-062, 3. Butane Tank PSV-068, 4. Regeneration Gas Heater PSV-750, b) On or about January 13, 2020, the employer did not perform inspections and testing on process equipment, including vessel alarms such as, but not limited to: 1. Deethanizer LAL-1100, 2. Deethanizer LSL-1100, 3. Deethanizer LAH-1100, 4. Deporpanizer LAL-1400 5. Deporpanizer LAH-1400 6. Debutanizer LAH-1500, 7. Debutanizer LAL-1500, c) On or about January 13, 2020, the employer did not perform inspections and testing on process equipment, including process equipment such as, but not limited to Heaters Burner Control DA 750. d) On or about January 13, 2020, the employer did not perform inspections and testing on process equipment, including process equipment such as, but not limited to emergency Shutdown Button(s).