Violation Detail
Standard Cited: 19100119 J04 II Process safety management of highly hazardous chemicals.
Inspection Nr: 1423074.015
Citation: 01006B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/15/2020
Nr Instances: 5
Nr Exposed: 8
Abatement Date: 02/25/2020
Gravity: 5
Report ID: 0521100
Contest Date:
Final Order: 02/11/2020
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 02/11/2020 | $0.00 | 02/25/2020 | Serious | |
| Penalty | Z: Issued | 01/15/2020 | $0.00 | 02/25/2020 | Serious |
Text For Citation: 01 Item/Group: 006B Hazard:
29 CFR 1910.119(j)(4)(ii): Inspection and testing procedures shall follow recognized and generally accepted good engineering practices: At a facility located at 191 W. 28th Avenue, Oshkosh, WI 54902; the inspections and testing procedure for equipment on the ammonia system did not follow recognized and generally accepted good engineering practices when: a) Procedures for inspecting pressure relieve valves conducted by Maintenance employees on a monthly basis were not consistent with the recommended inspection practices of the valves' manufacturer b) Procedures for monthly tests of ammonia sensors (RKI and Crowcon) were not consistent with the recommended inspection practices of the sensors' manufacturers. c) Procedures for the periodic change out of Crowcon ammonia sensor were not consistent with the recommended replacement periods of the sensor's manufacturer.