Violation Detail
Standard Cited: 19100119 F04 Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1231509.015
Citation: 01006B
Citation Type: Serious
Abatement Status:
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 11/08/2017
Nr Instances: 1
Nr Exposed: 7
Abatement Date: 01/02/2018
Gravity: 5
Report ID: 0521400
Contest Date: 12/04/2017
Final Order: 03/15/2019
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 03/15/2019 | $0.00 | 01/02/2018 | Serious | |
Penalty | C: Contested | 12/07/2017 | $0.00 | 01/02/2018 | Serious | |
Penalty | Z: Issued | 11/08/2017 | $0.00 | 01/02/2018 | Serious |
Text For Citation: 01 Item/Group: 006B Hazard:
29 CFR 1910.119(f)(4): The employer did not develop and implement safe work practices to provide for the control of hazards during operations such as lockout/tagout; confined space entry; opening process equipment or piping; and control over entrance into a facility by maintenance, contractor, laboratory, or other support personnel. On or about 5/10/2017, maintenance and operation employees routinely occupying the gas house were exposed to struck-by hazards when the Halon 1301 deflagration suppression system (DSS) was armed during entry. In the event of the system discharging, an oxygen deficiency environment could be created and debris/equipment could become missile fragments due to the pressure on the system. The employer did not develop and implement procedures for the control of hazardous energy when employees entered and performed routine work activities in the gas house. Abatement certification is required for this item in accordance with the requirements of 29 CFR 1903.19(c).