Violation Detail
Standard Cited: 19100119 J01 V Process safety management of highly hazardous chemicals.
Inspection Nr: 1123880.015
Citation: 01006B
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $25,000.00
Current Penalty: $0.00
Issuance Date: 08/01/2016
Nr Instances: 4
Nr Exposed: 9
Abatement Date: 08/22/2016
Gravity: 5
Report ID: 0213900
Contest Date: 08/08/2016
Final Order: 01/16/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 01/16/2018 | $0.00 | 08/22/2016 | Serious | |
Penalty | C: Contested | 08/10/2016 | $25,000.00 | 08/22/2016 | Repeat | |
Penalty | Z: Issued | 08/01/2016 | $25,000.00 | 08/22/2016 | Repeat |
Text For Citation: 01 Item/Group: 006B Hazard:
29 CFR 1910.119(j)(2): The employer did not establish written procedures to maintain the on-going integrity of process equipment: a) D2 Vinylidene Fluoride Process (VF2): The employer did not establish written procedures to maintain the on-going integrity of a high pressure alarm (PAHH-20509), a control device, on the first stage suction pressure of compressor K-201, on or about 2/9/16. b) D2 Vinylidene Fluoride Process (VF2): The employer did not establish written procedures to maintain the on-going integrity of an emergency shutdown switch, HS-206100, for the 200 area monomer distillation process, on or about 2/9/16. c) D2 Vinylidene Fluoride Process (VF2): The employer did not establish written procedures to maintain the on-going integrity of a level indicator control (LIC-20607), a control device, on condenser E-214 for distillation column C-201, on or about 2/9/16. d) D2 Vinylidene Fluoride Process (VF2): The employer did not establish written procedures to maintain the on-going integrity of C-112 the Drowning Tower, on or about 2/9/16. NOTE: IN ADDITION TO ABATEMENT CERTIFICATION, THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT DOCUMENTATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19. Solvay Specialty Polymers LLC USA was previously cited for a violation of this occupational safety and health standard or its equivalent standard 29 CFR 1910.119(j)(2), which was contained in OSHA inspection number 925822, citation number 1, item number 4 and was affirmed as a final order on 2/21/14 with respect to a workplace located at 17005 State Route 7 Marietta, OH 45750.