Standard Cited: 19100119 J05 Process safety management of highly hazardous chemicals.
Inspection Nr: 1081533.015
Citation: 01006B
Citation Type: Other
Abatement Status: Abatement Completed
Initial Penalty: $0.00
Current Penalty: $0.00
Issuance Date: 01/21/2016
Nr Instances: 1
Nr Exposed: 5
Abatement Date: 03/07/2016
Gravity:
Report ID: 0626000
Contest Date:
Final Order: 03/08/2016
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 03/08/2016 | $0.00 | 03/07/2016 | Other | |
| Penalty | Z: Issued | 01/21/2016 | $0.00 | 03/07/2016 | Serious |
Text For Citation: 01 Item/Group: 006B Hazard:
29 CFR 1910.119(j)(5): The employer did not correct deficiencies in equipment that are outside acceptable limits (defined by the process safety information in paragraph (d) of this section) before further use or in a safe and timely manner when necessary means are taken to assure safe operation. This violation was most recently observed on or about July 23, 2015 in the engine room when the employer failed to ensure the insulation on process piping such as but not limited to -49 F Recirculator Outlet to main liquid valve was repaired and sealed to prevent condensation and corrosion.