Violation Detail
Standard Cited: 19100119 F01 I D Process safety management of highly hazardous chemicals.
Inspection Nr: 329260.015
Citation: 01006A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,000.00
Current Penalty: $6,550.00
Issuance Date: 09/18/2012
Nr Instances: 1
Nr Exposed: 78
Abatement Date: 10/02/2012
Gravity: 10
Report ID: 0625700
Contest Date:
Final Order: 10/08/2012
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/08/2012 | $6,550.00 | 10/02/2012 | Serious | |
| Penalty | Z: Issued | 09/18/2012 | $7,000.00 | 10/02/2012 | Serious |
Text For Citation: 01 Item/Group: 006A Hazard:
29 CFR 1910.119(f)(1)(i)(D): The employer does not ensure that written operating procedures provide clear instructions for safely conducting activities involved in each covered process: This violation was observed on or about March 28, 2012, when it was observed that the employer had not included, in the T-7203A VCM Column Emergency Shutdown Procedure, the shutting off the chlorine vaporization feed by manual control and by the console controlled flow control (FIC-R7102A).
Translate