Violation Detail
Standard Cited: 19100106 C04 Flammable liquids.
Inspection Nr: 1776083.015
Citation: 01006A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $11,585.00
Current Penalty: $11,585.00
Issuance Date: 03/05/2025
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 04/21/2025
Gravity: 10
Report ID: 1032500
Contest Date: 03/31/2025
Final Order: 06/20/2025
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 06/20/2025 | $11,585.00 | 04/21/2025 | Serious | |
Penalty | C: Contested | 04/10/2025 | $11,585.00 | 04/21/2025 | Serious | |
Penalty | Z: Issued | 03/05/2025 | $11,585.00 | 04/21/2025 | Serious |
Text For Citation: 01 Item/Group: 006A Hazard:
29 CFR 1910.106(c)(4): Piping systems were not substantially supported and protected against physical damage and excessive stresses arising from settlement, vibration, expansion, or contraction. a) On September 11, 2024, and at times prior thereto, fuel receipt lines were attached to the outside wall of a building occupied by employees. The fuel lines were exposed to vehicles, settling of the building and vibration. Note: Certification of corrective action and supporting documentation are required for this item.