Violation Detail
Standard Cited: 19100303 B02 General.
Inspection Nr: 1638410.015
Citation: 01006A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $14,063.00
Current Penalty: $7,031.50
Issuance Date: 06/09/2023
Nr Instances: 7
Nr Exposed: 4
Abatement Date: 07/28/2023
Gravity: 10
Report ID: 0627100
Contest Date:
Final Order: 07/07/2023
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 07/07/2023 | $7,031.50 | 07/28/2023 | Serious | |
Penalty | Z: Issued | 06/09/2023 | $14,063.00 | 07/07/2023 | Serious |
Text For Citation: 01 Item/Group: 006A Hazard:
29 CFR 1910.303(b)(2): Listed or labeled electrical equipment was not used or installed in accordance with instructions included in the listing or labeling: On or about December 9, 2022 , in the Builder Shop, employees were plugging and unplugging various tools and equipment into metal junction boxes with prepunched knockouts installed as pendants. Instances include, but are not limited to the following: a) outlet box B1-5 providing power to equipment such as, but not limited to battery chargers b)outlet box G-11 providing power to equipment such as, but not limited to cell phone charges and sanders c) outlet box B1-1 providing power to equipment such as, but not limited to a fan d) outlet box B1-11, fan and sanders plug to these boxes e) outlet box providing power to dust collector located near Grizzly Industrial G0941 table saw f) outlet box G-3 providing power to equipment such as, but not limited to a Bosh Sander by "Do not Forklift" sign g) two metal outlet boxes with prepunched knockouts adjacent to Tank Room Pump disconnect used as pendants to provide power to sanders and extension cords