Violation Detail
Standard Cited: 19100305 B01 I Wiring methods, components, and equipment for general use.
Inspection Nr: 1580830.015
Citation: 01006A
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $7,458.00
Current Penalty: $5,000.00
Issuance Date: 08/26/2022
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 12/30/2022
Gravity: 5
Report ID: 0112000
Contest Date:
Final Order: 10/12/2022
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 10/12/2022 | $5,000.00 | 12/30/2022 | Serious | |
| Penalty | Z: Issued | 08/26/2022 | $7,458.00 | 10/14/2022 | Serious |
Text For Citation: 01 Item/Group: 006A Hazard:
29 CFR 1910.305(b)(1)(i): Conductors entering cutout boxes, cabinets, or fittings were not protected from abrasion, and openings through which conductors enter were not effectively closed. Maintenance Room - First Floor: On or about April 21, 2022, conductors entering control circuit panel cabinets mounted on the wall, and blocked by a workstation and cabinet, were not protected from damage while hanging out of the open face of the cabinet doors that were not effectively closed; moreover, non-metallic sheathed cables passed through holes in metal cabinets that were not provided with listed grommets or listed bushings to cover metal edges that would protect the passing cables from abrasion. The cabinets contained power, control, and communication wiring that controlled equipment throughout the facility.