Violation Detail
Standard Cited: 19260404 B01 II Wiring design and protection.
Inspection Nr: 1276626.015
Citation: 01006A
Citation Type: Serious
Abatement Date: 3
Initial Penalty: $3,696.00
Current Penalty: $2,217.60
Issuance Date: 03/05/2018
Nr Instances: 2
Nr Exposed: 11
Related Event Code (REC):
Gravity: 5
Report ID: 0316400
Contest Date:
Final Order: 03/28/2018
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 03/28/2018 | $2,217.60 | Serious | ||
Penalty | Z: Issued | 03/05/2018 | $3,696.00 | Serious |
Text For Citation: 01 Item/Group: 006A Hazard:
29 CFR 1926.404(b)(1)(ii): On a construction site, where an assured equipment grounding program was not utilized, all 120-volt, single-phase, 15 and 20 ampere receptacle outlets which were not a part of the permanent wiring of the building or structure and which are in use by employees did not have approved ground fault circuit interrupters for personal protection. (a) Old PSD Garage: On or about November 16, 2017, and times prior, employees were using tools and equipment on the jobsite, such as, a Dewalt circular saw, Dewalt angle grinders, and a Hilti chip hammer connected to extension cords that were plugged into a garage receptacle that was not equipped with GFCI protection. (b) Main Treatment Building: On or about November 20, 2017, and times prior, employees were using power tools, such as, a Dewalt circular saw, Dewalt drywall drill, Dewalt angle grinders, and a Hilti chip hammer connected to extension cords that were plugged into receptacles located in the 2nd story electrical room that were not equipped with GFCI protection.