Violation Detail
Standard Cited: 19100119 E03 III Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1269114.015
Citation: 01006A
Citation Type: Serious
Abatement Status:
Initial Penalty: $9,239.00
Current Penalty: $0.00
Issuance Date: 04/06/2018
Nr Instances: 1
Nr Exposed: 7
Abatement Date: 05/02/2018
Gravity: 5
Report ID: 0213900
Contest Date:
Final Order: 04/30/2018
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/30/2018 | $0.00 | 05/02/2018 | Serious | |
Penalty | Z: Issued | 04/06/2018 | $9,239.00 | 05/02/2018 | Serious |
Text For Citation: 01 Item/Group: 006A Hazard:
29 CFR 1910.119(e)(3)(iii) The process hazard analysis did not address engineering and administrative controls applicable to the hazards: a) GEA/FES and Frick ammonia refrigeration systems: The process hazard analysis failed to address how operators working on the roof will be notified of an emergency condition when there was inadequate reception for the wireless phones provided for communication and no alarm system on the roof, on or about 10/10/17. NOTE: THE EMPLOYER IS REQUIRED TO SUBMIT ABATEMENT CERTIFICATION FOR THIS ITEM. FAILURE TO COMPLY WILL RESULT IN AN ADDITIONAL PENALTY OF $1000.00 IN ACCORDANCE WITH 29 CFR 1903.19.