Violation Detail
Standard Cited: 19100119 D03 II Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1231509.015
Citation: 01006A
Citation Type: Serious
Abatement Status:
Initial Penalty: $9,054.00
Current Penalty: $0.00
Issuance Date: 11/08/2017
Nr Instances: 1
Nr Exposed: 7
Abatement Date: 01/02/2018
Gravity: 5
Report ID: 0521400
Contest Date: 12/04/2017
Final Order: 03/15/2019
Related Event Code (REC): C
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 03/15/2019 | $0.00 | 01/02/2018 | Serious | |
Penalty | C: Contested | 12/07/2017 | $9,054.00 | 01/02/2018 | Serious | |
Penalty | Z: Issued | 11/08/2017 | $9,054.00 | 01/02/2018 | Serious |
Text For Citation: 01 Item/Group: 006A Hazard:
29 CFR 1910.119(d)(3)(ii): The employer did not document that equipment complies with recognized and generally accepted good engineering practices. On or about 5/10/2017, employees routinely occupying the gas house were exposed to struck-by hazards when the Halon 1301 deflagration suppression system (DSS) was armed during entry. In the event of the system discharging, an oxygen deficiency environment could be created and debris/equipment could become missile fragments due to the pressure on the system. The employer did not comply with RAGAGEP, such as NFPA 69 (2014), Section 10.3, to ensure the system was disarmed during maintenance and operations prior to allowing employees to enter the gas house. Abatement certification is required for this item in accordance with the requirements of 29 CFR 1903.19(c).