Violation Detail
Standard Cited: 19100125 E01 I
Inspection Nr: 998042.015
Citation: 01006
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $3,080.00
Current Penalty: $2,156.00
Issuance Date: 03/18/2015
Nr Instances: 1
Nr Exposed: 2
Abatement Date: 05/28/2015
Gravity: 10
Report ID: 0523900
Contest Date:
Final Order: 04/02/2015
Related Event Code (REC):
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 04/02/2015 | $2,156.00 | 05/28/2015 | Serious | |
Penalty | Z: Issued | 03/18/2015 | $3,080.00 | 05/28/2015 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.125(e)(1)(i): All electrical wiring and equipment in each vapor area and any adjacent area did not conform to the applicable hazardous (classified) area requirements of subpart S: (a) Dip Tank Paint Building; Electrical outlets and boxes, adjacent to the blue dip tank, were not approved for the ignitable properties of flammable vapors; flammable paint utilized in this area had a flashpoint of 95 degrees Fahrenheit.