Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 315027003
Citation: 01006
Citation Type: Serious
Abatement Date: 05/05/2011 X
Initial Penalty: $7,000.00
Current Penalty: $4,250.00
Issuance Date: 04/11/2011
Nr Instances: 2
Nr Exposed: 625
Related Event Code (REC):
Gravity: 10
Report ID: 1032500
Contest Date:
Final Order:
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 05/02/2011 | $4,250.00 | 05/05/2011 | Serious | |
Penalty | Z: Issued | 04/11/2011 | $7,000.00 | 05/05/2011 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard: CHEMNEP
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location. a)Engine rooms: On or about December 14, 2010 and at times prior thereto, the engine room was not equipped with wiring classified for use in a Class 1, Division 2 location. b)LPR-2 Room: On or about December 14, 2010 and at times prior thereto, the engine room was not equipped with wiring classified for use in a Class 1, Division 2 location. Abatement Note: In lieu of installing classified wiring, the employer may ensure that an ammonia alarm is connected to the ventilation system, or that ventilation is constant with mechanical failure alarms per ASHRAE-15. Note: Abatement certification and supporting documentation are required for this item.