Violation Detail
Standard Cited: 19100119 E05 Process safety management of highly hazardous chemicals.
Inspection Nr: 313017774
Citation: 01006
Citation Type: Serious
Abatement Date: 11/10/2012 X
Initial Penalty: $7,000.00
Current Penalty: $7,000.00
Issuance Date: 06/21/2011
Nr Instances: 1
Nr Exposed: 5
Related Event Code (REC):
Gravity: 10
Report ID: 0524530
Contest Date: 07/13/2011
Final Order: 09/10/2012
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | F: Formal Settlement | 09/10/2012 | $7,000.00 | 11/10/2012 | Serious | |
Penalty | Z: Issued | 06/21/2011 | $7,000.00 | 08/05/2011 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard: CHEMNEP
29 CFR 29 CFR 1910.119(e)(5): The process hazard analysis team's finding was not resolved in a timely manner and the resolution was not documented: (a)The 2009 PHA team's recommendation #23 regarding re-configuration of hydrofluoric acid storage tanks U-613, U-404, and U-201 manual block valves located downstream of automatic dump valves had not been resolved. Abatement documentation is required for this item in accordance with the requirements of 29 CFR 1903.19(d).