Violation Detail
Standard Cited: 19100107 C06 Spray finishing using flammable and combustible materials.
Inspection Nr: 1808803.015
Citation: 01006
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,513.00
Current Penalty: $4,256.50
Issuance Date: 07/22/2025
Nr Instances: 2
Nr Exposed: 4
Abatement Date: 08/25/2025
Gravity: 5
Report ID: 0522500
Contest Date:
Final Order: 08/27/2025
Related Event Code (REC):
Emphasis:
| Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
|---|---|---|---|---|---|---|
| Penalty | I: Informal Settlement | 08/27/2025 | $4,256.50 | 08/25/2025 | Serious | |
| Penalty | Z: Issued | 07/22/2025 | $8,513.00 | 08/25/2025 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.107(c)(6): Electrical wiring, motors, and other equipment outside of but within twenty (20) feet of any spraying area, and not separated therefrom by partitions, shall not produce sparks under normal operating conditions and shall otherwise conform to the provisions of subpart S of this part for Class I, Division 2 Hazardous Locations. a. Located in the Color Lab: On or about March 6, 2025, electrical equipment within the color lab, including disconnect switches, outlets, drying rack, and mixing station, was not rated for use in a hazardous location, which created a potential fire hazard. b. Located in the Blending Room: On or about March 6, 2025, electrical equipment within the blending room, including disconnect switches, outlets, drying rack, and mixing station, was not rated for use in a hazardous location, which created a potential fire hazard.
Translate