Violation Detail
Standard Cited: 19100119 J04 III Process safety management of highly hazardous chemicals.
This violation item has been deleted.
Inspection Nr: 1803784.015
Citation: 01006
Citation Type: Serious
Abatement Status:
Initial Penalty: $16,550.00
Current Penalty: $0.00
Issuance Date: 07/01/2025
Nr Instances: 3
Nr Exposed: 2100
Abatement Date: 08/18/2025
Gravity: 10
Report ID: 0830500
Contest Date:
Final Order: 08/04/2025
Related Event Code (REC): C
Emphasis:
Substance: 0170
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 08/04/2025 | $0.00 | 08/18/2025 | Serious | |
Penalty | Z: Issued | 07/01/2025 | $16,550.00 | 08/18/2025 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.119(j)(4)(iii): The frequency of inspections and tests of process equipment was not consistent with applicable manufacturers' recommendations and good engineering practices, and more frequently if determined to be necessary by prior operating experience: Cargill, Inc. DBA Cargill Meat Solutions Corporation, 1505 East Burlington Avenue Fort Morgan, CO 80701: The employer did not ensure that employees were protected from inhalation hazards associated with ammonia from the following conditions: (a) On or about February 6, 2025, the employer did not perform the required inspections of insulated piping for piping lines CS 100 and 101 located on the penthouse roof as required by IIAR 6, Table 11.1. (b) On or about February 10, 2025, the employer did not perform the required annual inspection for a Henry Technology Pressure Relief Valve (serial number 1422, category 5602, size ? inch, set PSI 250, capacity 57.7) as required by IIAR 6, Table 13.1. (c) On or about February 10, 2025, the employer did not perform the required annual inspection for a Henry Technology Pressure Relief Valve (serial 1419, category 5602, size ? inch, set PSI 250, capacity 57.6) as required by IIAR 6, Table 13.1.