Violation Detail
Standard Cited: 19100307 C Hazardous (classified) locations.
Inspection Nr: 1710693.015
Citation: 01006
Citation Type: Serious
Abatement Status: Abatement Completed
Initial Penalty: $8,067.00
Current Penalty: $2,000.00
Issuance Date: 05/13/2024
Nr Instances: 4
Nr Exposed: 12
Abatement Date: 02/03/2025
Gravity: 5
Report ID: 0111400
Contest Date:
Final Order: 06/12/2024
Related Event Code (REC): R
Emphasis:
Type | Latest Event | Event Date | Penalty | Abatement Due Date | Citation Type | Failure to Abate Inspection |
---|---|---|---|---|---|---|
Penalty | I: Informal Settlement | 06/12/2024 | $2,000.00 | 02/03/2025 | Serious | |
Penalty | Z: Issued | 05/13/2024 | $8,067.00 | 07/03/2024 | Serious |
Text For Citation: 01 Item/Group: 006 Hazard:
29 CFR 1910.307(c): Equipment, wiring methods, and installations of equipment in hazardous (classified) locations were not intrinsically safe, approved for the hazardous (classified) location, or safe for the hazardous (classified) location: Production Area: Where combustible dust generated by the manufacturing of fiberglass products was present, electrical equipment were not intrinsically safe, approved for a Class II, Division I, location, or safe for a Class II, Division I, location, on or about November 29, 2023: (a) Robot (cutting) Room - Electrical equipment including, but not limited to, normal lighting snap switches and overhead lighting were located were not intrinsically safe, approved for a Class II, Division I, location, or safe for a Class II, Division I, location, on or about November 29, 2023. (b) Storage (electrical equipment) Room adjacent to the Robot (cutting) Room - Electrical equipment including, but not limited to, overhead lights, circuit breaker panels, disconnect switches and outlets, in Class II, Division I, locations, was not intrinsically safe, approved for a Class II, Division I, or safe for a Class II, Division I, location, on or about November 29, 2023. (c) Robot (cutting) Room and Cutting Booth - A vacuum used in a Class II, Division 1 location was not intrinsically safe, approved for a Class II, Division 1, location, or safe for a Class II, Division 1, location on or about November 29, 2023. d) Adjacent to Cutting Booth - electrical equipment used to energize the Donaldson Torit dust collectors and other electrical equipment attached to the right Donaldson Torit dust collector to energize equipment such as the hoist/lift was not intrinsically safe, approved for a Class II, Division 1, location, or safe for a Class II, Division 1, location on or about November 29, 2023.